DCD-CE3(WHT)

Shipping in
48h
  • Conventional combined heat detector 90 grad
  • Twin LEDs allow a display of 360°
  • (9.5 ~ 30 V dc)
  • Requires YBN-R base 3
  • Remote indicator output
  • Description
  • Specifications
  • Contents
  • Downloads

DCD-CE3 is a thermovelocimetric detector with a fixed temperature element of 90 °C that uses a thermistor and a linearization circuit to provide an accurate linear response

Ideal for use where smoke detectors are not suitable due to the presence of steam or cooking fumes.

It is compatible with a wide range of bases for different applications and these are compatible with most conventional systems.

A third terminal provides a remote indicator output


  • HOCHIKI
  • Conventional combined heat detector 90 degrees white
  • Variable sensitivity
  • Remote indicator output
  • (9.5 ~ 30 V dc)
ReferenceDCD-CE3(WHT)
Operating voltage9.5 - 30 V dc
Quiescent current (typ. ) 35 μA (typical)
Maximum alarm current (typ.)40 mA
Remote indicating unit 20 mA (max.) 9,5-14 mA
Operating temperature range-10 + 50
Storage temperature range-30 to +70
Maximum humidity 95% RHNon-condensing (at 40 C)
Input protection classification IP63
Color / material boxivory or white / polycarbonate
Weight (g) / Diameter (mm) / Height (mm)76 / 100 / 38
Supported basesYBN-R6, YBN-R/6SK, YBO-R/6R, YBO-R/6RS, YBO-R/6RN, YBO-R/6PA
Base fixing centers (mm) 48 ~ 74
Certificates(EN54:2000) Class A1 & A1R LPCB
  • Conventional combined heat detector 90 degrees

alt