LAAEE11010H1HEUK1

  • Addressable fire panel of 2 loops
  • Power Supply 5.25A
  • Loop current of 500 mA
  • 4 siren circuits and 5 programmable relays
  • Resistive touch screen
  • Extendable up to 8 loops
  • Description
  • Specifications
  • Contents
  • Downloads

Hochiki's Latitude Fire Panel offers flexible fire detection control for medium to large facilities.

This versatile system supports from 2 expandable to 8 loops thanks to the K758, loop cards with capacity for up to 1.000 devices. Intuitive touch-screen interface simplifies operation and configuration. The panel has robust networking capabilities, allowing the integration of up to 127 panels. Latitude panel ensures accurate alarm management.

Compatible with wide range of ESP sensors, modules and alarm equipment

hochiki, provides a comprehensive fire protection solution.

The system's expandability and backward compatibility make it an ideal choice for both new installations and system upgrades.


  • HOCHIKI
  • Addressable fire control panel of 2 loops expandable to 8
  • Loop current of 500 mA
  • Certificates EN54-2, EN54-4, EN54-13
  • Power supply 5.25A
ReferenceLAAEE11010H1HEUK1
Battery capacityUp to 26 Ah
Supply voltage 230 VAC or 115 VAC
Power supply A 24 V DC 5,25 A (charge up to 26 Ah)
Certificates EN54-2, EN54-4, EN54-13
LCD screenColour 800 x 480 with resistive touch screen and automatic backlight dimming
Printer of 40 columns, front-loading thermal (optional)
LED zone indicators Up to 3 banks of 48 (144) (optional)
Software zones 2000
Software groups 5000
Event registration 10.000 events, resolution of 1 second. Filterable and printable
Detection loopsFrom 2 to 8 expandable with (K758 card from 2 loops)
Detection loop current 500 mA each
Siren circuits, 4 each rated 2,5 A, 24 V DC, programmable
Auxiliary supply of 24 V 1 24 V DC with fuse of 500 mA
Auxiliary supply of 24 V 2 24 V DC with fuse of 500 mA
Default Relays Failure, Fire, Alarm, Programmable 1 and Programmable 2 (all reprogrammable)
Programmable inputs 3, activated by volt-free contacts.
Auxiliary serial port A RS232 programmable
Auxiliary serial port B RS232 programmable
Serial fire routing port (Ifam)RS485 programmable
USB host port USB type A
USB device port USB type B
Dimensions 20mm (W) x 585mm (H) x 145mm (D)
MaterialSteel sheet 1,5 mm.
Finished Epoxy powder coated.
Color - Lid and Box BS 00 A 05 fine texture
Weight (kg) 20
Fire routing output Supervised
Fire routing input Supervised
Fault routing output Supervised
Fault routing input Supervised
Extinguisher outlet Supervised
Fire extinguisher input Supervised
Extinguisher fault input Supervised
  • Addressable fire panel of 2 loops